交联聚乙烯绝缘电力电缆3.6/6KV-26/35KV(Power cables with XLPE insulated)
一、型号及名称(Models and names)
型号
|
名称
|
YJV
|
铜芯交联聚乙烯绝缘聚***护套电缆
|
YJY
|
铜芯交联聚乙烯绝缘聚乙烯护套电缆
|
YJLV
|
铝芯交联聚乙烯绝缘聚***护套电缆
|
YJLY
|
铝芯交联聚乙烯绝缘聚乙烯护套电缆
|
YJV22
|
铜芯交联聚乙烯绝缘钢带铠装聚***护套电缆
|
YJV23
|
铜芯交联聚乙烯绝缘钢带铠装聚乙烯护套电缆
|
YJLV22
|
铝芯交联聚乙烯绝缘钢带铠装聚***护套电缆
|
YJLV23
|
铝芯交联聚乙烯绝缘钢带铠装聚乙烯护套电缆
|
注:1、阻燃型电缆在以上交联聚乙烯绝缘子电力电缆的前面加ZA、ZB、ZC:WDZA、
WDZB、WDZC。
WDZB、WDZC。
二、用途
本产品适用于额定电压为3.6/6KV(7.2KV)到26/35KV(40.5KV)的配电线路。阻燃电缆用于对阻燃性能有较高的要求的场合。
三、制造依据
本产品依据GB/T 12706.2.3-2002制造。
四、使用特性
1、电缆导体的***高额定温度为90℃。
本产品依据GB/T 12706.2.3-2002制造。
四、使用特性
1、电缆导体的***高额定温度为90℃。
2、短路时(***长持续时间不超过5秒)电缆导体的***高温度不超过250℃。
3、电缆数设时的环境温度应不低于0℃。其***小弯曲半径如下:
单芯无铠装电缆:20D
单芯有铠装电缆:15D
三 芯无铠装电缆:15D
三芯无铠装电缆:12D
注:D为电缆外径
单芯无铠装电缆:20D
单芯有铠装电缆:15D
三 芯无铠装电缆:15D
三芯无铠装电缆:12D
注:D为电缆外径
Names and Models
Model
|
Name
|
YJV
|
Copper conductor XLPE insulated PVC sheathed power cable
|
YJY
|
Copper conductor XLPE insulated PE sheathed power cable
|
YJLV
|
Aluminum conductor XLPE insulated PVC sheathed power cable
|
YJLY
|
Aluminum conductor XLPE insulated PE sheathed power cable
|
YJV22
|
Copper conductor XLPE insulated, steel tape armored, PVC sheathed power cable
|
YJV23
|
Copper conductor XLPE insulated, steel tape armored, PE sheathed power cable
|
YJLV22
|
Aluminum conductor XLPE insulated, steel tape armored, PVC sheathed power cable
|
YJLV23
|
Aluminum conductor XLPE insulated, steel tape armored, PE sheathed power cable
|
Note
|
flame retardant cable, plus ZA,ZB,ZC,WDZA,WDZB,WDZC before the type of the XLPE insulated power cables
|
Usages
These products are produced in accordance to GB/T 12706.2.3-2002.They apply to the tran***ission and distribution lines while rated voltage from 3.6/6KV to 26/35KV, while flame retardant power cables are used in the places with special demands of flame retardant property.
Features
1.Maximum rated temperature of cable is 90℃.
These products are produced in accordance to GB/T 12706.2.3-2002.They apply to the tran***ission and distribution lines while rated voltage from 3.6/6KV to 26/35KV, while flame retardant power cables are used in the places with special demands of flame retardant property.
Features
1.Maximum rated temperature of cable is 90℃.
2.Maximum conductor temperature is lower than 250℃ when cable is shorted for less than 5 seconds.
3.Ambient temperature is not lower than 0℃ and its minimum bending radius is as follows when cable is installed:
1 core cable: 20D
1 core armored cable: 15D
1 core armored cable: 15D
3 cores cable:15D
3 cores armored cable: 12D
Noted: D for exterior diameter of cable.