- Bare copper conductor, solid or stranded, to DIN VDE 0295 cl. 1 or cl. 2, BS 6360 cl. 1 or 2, IEC 60228 cl. 1 or cl. 2, HD 383
- Double conductor insulation of mica tape and cross-linked polymer HI1, to DIN VDE 0207 part 23
- Color coding of conductors according to DIN VDE 0293-308
- Each single conductor covering with flame resistant glass-fibre tape
- Conductors stranded in layer
- Conductor wrapping with glass-fibre tape as flame-protection
- Outer jacket orange, polyolefin compound HM4, to DIN VDE 0207 part 24
Tests
- Flame test to DIN VDE 0482 part 266-2/ HD 405.3, BS 4066 part 3/ EN 50266-2/ IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C)
- Corrosiveness of combustion gases according to DIN VDE 0482 part 267/ EN 50267-2-2/ IEC 60754-2 (equivalent DIN VDE 0472 part 813)
- Halogen-free according to DIN VDE 0482 part 267/ EN 50267-2-1/ IEC 60754-1 (equivalent DIN VDE 0472 part 815)
- Smoke density according to DIN VDE 0482 part 1034-1+2, HD 606, DIN EN 61034-1+2/ IEC 61034-1+2, BS 7622 part 1+2 (equivalent DIN VDE 0472 part 816)
- Insulation integrity under flame propagation to VDE 0472 part 814 IEC 60331
- Burning behavior in fire (functionality) of the complete cable system to DIN 4102 part 12 (90 minutes)
- LS0H = Low Smoke Zero Halogen
|
|
|
- Halogen-free; no evolution of corrosive and toxic gases
- Flame retardant
- Hardly flammable
- Self-extinguished and fire resistant
- No flame propagation, therefore security from fire
- Low smoke density, no darkening of emergency exits without hindering the fire extinguishing works
- Toxicological harmless
- No self-ignition
- Maintenance of functionality during the increased current load
- FE 180: Insulation integrity for 180 minutes. Tests to DIN VDE 0472 part 814 IEC 60331.
Insulation integrity under direct flame propagation for the test period of 180 minutes.
- E 90: Functionality of electrical cable systems for minimum 90 minutes. Test method to DIN 4102 part 12. This fulfils the demands of technical guide lines for fire protection (supplement 1 to DIN VDE 0108 part 1).
The functionality for 90 minutes assures the functional performance of water-pressure-rising stations for the supply to avoid smoke and heat in safety-stairs and inner rooms, ladder shafts and engine rooms for fire brigade lifts, emergency lifts for sickbeds in hospitals and the fire brigade lifts.
|
|
|
|
- RE = round conductor, multiple-wire;
RM = round conductor, single-wire.
|
|
Everywhere, where in case of fire human life and material assets are to be protected and safety consciousness take a special significance, e.g. in industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN VDE 0107), department stores, data processing centers, theaters, cinemas, in multi-story buildings, public gatherings, schools etc. (DIN VDE 0108), mining works, offshore plants, leading centers, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in dry and moist rooms, in, above, on and beneath plaster as well as in walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes.
Additionally valid also DIN VDE 0298 part 1 and 2.
For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
|
|
|
|