Compact 6 DIN modules size
True RMS measurement
More than 50 electrical parameters displayed
Neutral current monitoring
Bi-directional, four quadrants values on serial
communication port
High contrast bright LED display
Up to 6 measurement values displayed
simultaneously
Power and current demand calculation during userdefinable
time period
No PTs required up to 600 (750) VAC
Programmable CT ratio
Easy to use
Specificati***
Power supply
Rated voltage: 115 VAC / 230 VAC +15% -20%
C***umption: 2 VA max
Voltage inputs
Maximum measurable voltage: 600 (750) VAC max L-L
Input impedance: ›1.3 MOhm
Burden: max 0.15 VA per phase
Frequency: 45 - 65 Hz
Current inputs
Rated current (Ib): 5 ARMS
Min / max measurable current: 20 mA / 7 ARMS
Maximum overload: 10 ARMS continuous - 100 ARMS for 1 sec.
Input impedance: 0.02 Ohm approximately
Burden: max 0.5 VA per phase
Insulation voltage: 150 VAC max between phases
Rogowski input: 200÷49995 A on request
Typical accuracy
Voltage: &plu***n;0.3% reading &plu***n;0.05% full scale
Current: &plu***n;0.5% reading &plu***n;0.05% full scale (5 Arms)
Active power: &plu***n;1% reading &plu***n;0.2% full scale (PF=1)
Power factor: &plu***n;1.5% reading (0.5 inductive - 0.8 capacitive)
Active energy: &plu***n;1.5% reading (0.5 inductive - 0.8 capacitive)
Frequency: &plu***n;0.05% reading &plu***n;1 digits from 45 to 65 Hz
Display and operating controls
Display: high brightness 10 mm LED display
6 lines, 3 digits
Keypad: 3 push-butt***
Communication port
Type: RS232 or RS485 on request, optoisolated
Baud rate: 300 to 57600 bps
Digital outputs
Type: 2 optoisolated (50V-100mAAC-DC)
Environmental conditi***
Operating temperature: from -20°C to +60°C
Storage temperature: from -30°C to +75°C
Relative humidity: 80% max. without condensation
Mechanical characteristics
Material: plastic enclosure - noryl UL94-V0
Protection degree: IP20
Terminals: conductors 2.5 mm2
Size / weight: 106x90x57 mm / 300 gr
Standa*** compliance
Safety: 73/23/EEC and 93/68/EEC directives,
EN61010.1 safety standard
EMC: 89/366/EEC directive and following
modificati*** 93/31/EEC and 93/68/EEC,
EN50081-2, EN50082-2, EN61326/A1